Dennis Comment by Dennis on July 13, 2009 at 6:03am
Pre pasensya na sobrang busy ko ngayon nagkaroon ng chance na makapag bukas ng site. Bro walang slide valve itong model na ito VSD ang compressor nito. Ang sinasabi yung YCAS na model. Merong problema sa commissioning ng chiller pag naputol ang spring. Mostly na nakakalimutan tanggalin ang shipping bolt ng compressor during commissioning. Meron ding unloader spring na mas malambot ang tention pag hindi nagload ng 100% ang compressor.
Danz Comment by Danz on June 9, 2009 at 3:59pm
Pare nagbukas kami nila Jake Roxas na ganyan compressor karamihan sa slide valve ang tama pera sa bearing. Mahina yata sa slide valve yan kundi putol yung spring o basag yung piston madalas encounter namin.
JEPER M.PARDE Comment by JEPER M.PARDE on June 5, 2009 at 4:17pm
Sir any chance that we can repair this compressor on site?
To download books, reference manuals and softwares, movies and many more, just proceed to download center.

To advertise on this network, just proceed to our Buy from 2CO counter.

2CheckOut.com Inc. (Ohio, USA) is an authorized retailer for goods and services provided by HVAC Philippines. Contact Chillerman for details.

Forum

Nestor Molato

how is the capacity slide inside the screw compressor function. 14 Replies

Started by Nestor Molato. Last reply by Nestor Molato 1 day ago.

Nestor Molato

??Procedures on Start up and Commissioning of Bitzer Screw Compressor CSH8561-125Y?? 9 Replies

Started by Nestor Molato. Last reply by Nestor Molato 1 day ago.